Saturday, June 5, 2010

The Most Common Repair for Boilers in Minneapolis

While boilers aren't commonly used for new homes in Minnesota, there are still plenty of houses in Minneapolis and Saint Paul that rely on boilers for heat.  I'm a big fan of boilers - so much so that I even wrote a blog about why I like them more than furnaces (boilers vs furnaces)

For Minneapolis homes that have boilers, the most common required repair for Truth-in-Housing Evaluations is a missing or improper backflow prevention device installed on the water line that feeds the boiler.  This repair also requires a permit.

The photos below show improper installations that would require repair. Click on the photos for a larger version.

Missing_Backflow_Preventer Single_Check_Valve

Backflow preventers are needed on boilers to prevent the water that flows throughout the radiators from potentially mixing with the city's potable water supply and contaminating it.

In Minnesota, the minimum type of backflow prevention device required for a boiler in a one or two-family home is a Double Check Valve with an Intermediate Atmospheric Vent(DCVIAV).  These are often referred to as "9D Valves" because Watts makes one of these valves, and their part number is 9D.  You know you have the market cornered when everyone calls the product by your part number, right?



Watts 9D Valve
Dual Check Valve with an Intermediate Atmospheric Vent

These valves are special because they're almost 100% fail-safe.  Even if both of the internal check valves were to become fouled and stuck in an open position, the vent would still prevent any water that was subject to backpressure from potentially contaminating the potable water supply - this water would just leak out of the vent.

Because the vent has the possibility of leaking water, most plumbers will install a pipe off the vent to direct water to a location where it won't cause damage.  This is also part of the installation instructions for these valves.

For anything other than a one or two-family home, Minnesota requires a Reduced Pressure Zone (RPZ) valve on the water supply for the boiler.  These are also required when any chemicals are added to the system, such as glycol.  RPZ valves must be tested every year, and must be re-built every four years.  When I inspect larger multi-family dwellings in Minneapolis and Saint Paul, I check the RPZ valves to make sure they have appropriate documentation showing that they've been properly serviced.
For a full list of the types of backflow prevention devices required in Minnesota, click here https://www.revisor.mn.gov/rules/?id=4715.2110 .

For more information on common Truth In Sale of Housing defects, click on any of the links below.



Reuben Saltzman, Structure Tech Home Inspections - Email - Truth In Housing Minneapolis

Facebook Reuben's LinkedIn Page Follow StructureTech on Twitter ASHI Certified Home Inspector - Click To Verify Click to subscibe to Reuben's Blog

Saturday, May 8, 2010

A Missing Jumper Wire At The Water Meter

One of the most common electrical defects that I find while doing Truth-In-Sale of Housing Evalutions in Minneapolis is a missing jumper wire at the water meter.  This is a required repair item, and I often find the repair done improperly, so I'm writing this blog to help anyone that has to fix this item.
To start, here is the wording that TISH Evaluators are supposed to follow, which comes directly from the Minneapolis TISH Evaluator Guidelines (2008):

A) There must always be a jumper wire installed around the water meter. Bonding jumpers shall be of copper or other corrosion-resistant material, have approved clamping devices and be of the correct wire gauge for the service installed. If this jumper wire is not present or is not properly connected on either side of the water meter, (or only the street side, when the water pipes are Pex or similar materials) or is not installed with approved materials, mark as RRE. Be specific on what work is needed


A jumper wire is used to electrically bond the water distribution pipes throughout the house.  The purpose of bonding the water distribution piping in the home is to make sure they can't accidentally become energized.  If an ungrounded (aka - hot) conductor came in contact with a properly bonded water pipe, the current would have such a good path back to the main panel that it would overload the circuit breaker and the breaker would quickly trip.  In other words, it protects against electric shocks.


A much more important reason that Minneapolis requires a jumper wire at the water meter is that it was once acceptable for the electric service to use the water distribution piping in the house as a grounding conductor.  I couldn't find any great diagrams that showed this type of installation, so I made my own crude diagram.  Don't make fun of my drawing - I know I'm no artist or architect!
Jumper Wire

And here's a photo of what this looks like.
Jumper Wire Photo with labels

The problem with this installation is that if the water piping gets disconnected, the electric panel is no longer grounded to the water piping.  That's why this installation is no longer acceptable.  Many old homes in Minneapolis are still wired this way, so it's especially important for the jumper wire to be present at these houses.

If there is any other break in the water distribution pipes (ie - plastic water piping, plastic water filter, water softener, etc), there needs to be a jumper installed.  For a blog specifically talking about this topic, check out Seattle Home Inspector Charles Buell's blog on jumper wires.

The photos below show what a proper jumper wire should look like.   While some TISH evaluators require the bonding clamps to be placed on the outsides of the shutoff valves (vs right next to the meter), I don't.  This might be the preferred method, but that's all - it's not a requirement.  As always, click the photos for a larger version.
Jumper Wire at Meter
Ground Clamp



For more information on common Truth In Sale of Housing defects, click on any of the links below.
Reuben Saltzman, Structure Tech Home Inspections - Email - Truth in Housing Evaluator
Facebook Reuben's LinkedIn Page Follow StructureTech on Twitter ASHI Certified Home Inspector - Click To Verify Click to subscibe to Reuben's Blog